某110kV变电站电气主接线设计方案 联系客服

发布时间 : 星期日 文章某110kV变电站电气主接线设计方案更新完毕开始阅读2af6c227534de518964bcf84b9d528ea81c72fa3

图4-5 d4点短路图

d4:

X19?X1?X2//X3//X4//X5?(X10?X11)//(X9?X12)1?0.1224??0.17862?0.2117Xsj4?X19?Sex2000?0.2117??4.234 Sj10011??4.7236 X190.2117

I0??I1??I2??I0?I1?I2?I0??Ij?4.7236?5.5?25.98(kA)

ich?2.55?I0?2.55?25.98?66.249(kA) Ich?1.51?I0?1.51?25.98?39.2298(kA) Sd?I0??Sj?4.7236?100?472.36(MVA)

5、短路点d5:

图4-6 d5点短路图

d5:

X20?X1?X2//X3//X4//X5?(X9?X13)//(X10?X14)1?0.1224???0.1786?0.1151?2?0.2693Xsj5?X20?Sex2000?0.2693??5.386 Sj100

I0??I1??I2??11??3.713 X200.2693I0?I1?I2?I0??Ij?3.713?1.56?5.792(KA)

ich?2.55?I0?2.55?5.792?14.7696(kA) Ich?1.51?I0?1.51?5.782?8.7459(kA) Sd?I0??Sj?3.713?100?371.3(MVA)

6、短路点d6:

d6:

X21?X20?X15?0.2693?0.5551?0.8244

Xsj6?X21?Sex2000?0.8244??16.488 Sj10011??1.213 X210.8244I0??I1??I2??I0?I1?I2?I0??Ij?1.213?1.56?1.8923(kA)

ich?2.55?I0?2.55?1.8923?4.8254(kA) Ich?1.51?I0?1.51?1.8923?2.8574(kA) Sd?I0??Sj?1.213?100?121.3(MVA)

短路电流计算成果,汇总如表4-1所示

短路编号点 短路平均电压Uj(KV)基准电分支电流Ij(KA) 短路电流值 短路电流标幺值I0? I0(KA)抗X? ich(KA)Ich(KA)Sd(MVA)

d1 d2 d3 115 10.5 10.5 10.5 37 37 0.502 0.1224 0.416 5.5 5.5 5.5 1.56 1.56 4.177 10.651 6.307 813.99 5.097 3.0185 36.3 292 2.7514 0.3635 1.999 0.3424 2.9214 16.068 40.972 24.263 d4 d5 d6 0.2117 4.7236 25.98 66.249 39.229 472.36 0.2693 3.713 5.792 14.769 8.746 371.3 0.8244 1.213 1.8923 4.8254 2.8574 121.3 4.3 本章小结

短路是电力系统的严重故障。短路冲击电流、短路电流的最大有效值、短路容量是校验电气设备的重要数据。

对于简单的电力系统,可以采用网络变换与化简计算短路电流。计算时,首先作出整个系统的等值电路,然后进行网络变换与化简,将网络化简成只保留电源节点和短路点。要求短路电流,最关键的是根据网络化简求出电源点对短路点的转移阻抗或输入阻抗。